CAD (0)
  • Cart is empty
Air Cooled, non water heating assist dehumidifiers are used when there is a primary pool and spa water heating source such as a hot water boiler in place.Typical applications would include, but be limited to, small pool surface area projects or in coldclimates or both.
Unit of Measure

Available Model Configurations

N/A DCA9000Y: Air Cooled DCA9000Y-CT: Water Cooled

Standard Features

N/A

 - 3 Year Parts Warranty  - Dual Refrigeration Circuit  - Dual Scroll Compressor  - ElectroFin Coated Coils  - Low Ambient Head Pressure Control  - Listed to UL 60335-2-40  - Motorized Evaporator Bypass Damper  - Powder Coated, Galvannealed Steel Cabinet  - Remote Condenser Ready  - Rifle Tube Refrigeration Coils  - Stainless Steel Condensate Drain Pan  - Standard Microprocessor Control System (WH Models only)  - TEFC Blower Motor

Optional Features

N/A

 - Control Options  - Defrost Timer Package  - External Static Upgrade  - Other Options Available  - Outdoor Installation Package  - Outdoor Make Up Air Assembly with Damper & Filter  - Remote Ready Delete  - Right Side Component Service Access  - Space Heating Options Available  - Top or Bottom Discharge (Not Field Convertible)  - Water Cooled Condenser for Water Heating or A/C Available

Available Voltage/Phase

N/A 208/230-3-60 460-3-60 575-3-60

Compressor @ 208/230-3-60 A/B

N/A 125 / 125 MBH33.3 / 33.3 RLA255 / 255 LRA

Blower Motor @ 208/230-3-60

N/A 7.5 hp20.0 Unit FLA

Unit FLA @ 208/230-3-60

N/A 88.8

Maximum Fuse Size @ 208/230-3-60

N/A 125

Minimum Circuit Ampacity @ 208/230-3-60

N/A 97.1

Operating Power @ 208/230-3-60

N/A 24.62 kW

Compressor @ 460-3-60 A/B

N/A 125 / 125 MBH15.4 / 15.4 RLA140 / 140 LRA

Blower Motor @ 460-3-60

N/A 7.5 hp9.5 Unit FLA

Unit FLA @ 460-3-60

N/A 41.3

Maximum Fuse Size @ 460-3-60

N/A 60

Minimum Circuit Ampacity @ 460-3-60

N/A 45.2

Operating Power @ 460-3-60

N/A 24.31 kW

Compressor @ 575-3-60 A/B

N/A 125 / 125 MBH12.9 / 12.9 RLA107.6 / 107.6 LRA

Blower Motor @ 575-3-60

N/A 7.5 hp7.6 Unit FLA

Unit FLA @ 575-3-60

N/A 34.3

Maximum Fuse Size @ 575-3-60

N/A 45

Minimum Circuit Ampacity @ 575-3-60

N/A 37.5

Operating Power @ 575-3-60

N/A 24.31 kW

CFM

N/A 9000

Nominal Tonnage

N/A 2 x 10.2 Dual Circuit
Moisture Removal @ 82°DB / 50% R.H.1 N/A 91.7 LB/HR

Moisture Removal @ 82°DB / 60% R.H.1

N/A 117.2 LB/HR
Sensible Cooling @ 82°DB / 50% R.H.2 N/A 144.6 MBH

Sensible Cooling @ 82°DB / 60% R.H.2

N/A 127.3 MBH

Weight

N/A 2900 LB

External Static Pressure

N/A 1.00 " H2O

Refrigerant

N/A R-454B (Factory Charged A/B 65 lbs.)

Compressor Type

N/A Dual Scroll

Filter (Quantity: 6)

N/A 20" x 25" x 4" Pleated

Drain Connection

N/A 1" Bar Drain

Liquid Inlet A/B [O.D.] (up to 50')

N/A 0.75/0.75 in

Hot Gas Outlet A/B [O.D.] (up to 50')3

N/A 1.125/1.125 in

Note

N/A Ratings are subject to change without notice
  • 1 Reheat Mode assuming 1050 BTU/lb
  • 2 Cooling Mode with Remote Condenser at 95 °F