Air Cooled, non water heating assist dehumidifiers are used when there is a primary pool and spa water heating source such as a hot water boiler in place.Typical applications would include, but be limited to, small pool surface area projects or in coldclimates or both.
Unit of Measure

Available Model Configurations

N/A DCA3600Y: Air Cooled DCA3600Y-CT: Water Cooled

Standard Features

N/A

 - 3 Year Parts Warranty  - ElectroFin Coated Coils  - Low Ambient Head Pressure Control  - Listed to UL 60335-2-40  - Motorized Evaporator Bypass Damper  - Powder Coated, Galvannealed Steel Cabinet  - Remote Condenser Ready  - Rifle Tube Refrigeration Coils  - Single Refrigeration Circuit  - Single Scroll Compressor  - Stainless Steel Condensate Drain Pan  - Standard Microprocessor Control System (WH Models only)  - TEFC Blower Motor

Optional Features

N/A

- Control Options  - Defrost Timer Package  - Extended Surface Filters 2" & 4"  - External Static Upgrade  - Other Options Available  - Outdoor Installation Package  - Outdoor Make Up Air Assembly with Damper & Filter  - Remote Ready Delete  - Right Side Component Service Access  - Space Heating Options Available  - Top or Bottom Discharge (Not Field Convertible)  - Water Cooled Condenser for Water Heating or A/C Available

Available Voltage/Phase

N/A 208/230-3-60 460-3-60 575-3-60

Compressor @ 208/230-3-60

N/A 91800 BTU28.7 RLA207.5 LRA

Blower Motor @ 208/230-3-60

N/A 2 hp6.6 Unit FLA

Unit FLA @ 208/230-3-60

N/A 37.0

Maximum Fuse Size @ 208/230-3-60

N/A 60

Minimum Circuit Ampacity @ 208/230-3-60

N/A 44.2

Operating Power @ 208/230-3-60

N/A 8.66 kW

Compressor @ 460-3-60

N/A 91800 BTU12.4 RLA100.2 LRA

Blower Motor @ 460-3-60

N/A 2 hp2.9 Unit FLA

Unit FLA @ 460-3-60

N/A 16.1

Maximum Fuse Size @ 460-3-60

N/A 30

Minimum Circuit Ampacity @ 460-3-60

N/A 19.2

Operating Power @ 460-3-60

N/A 8.42 kW

Compressor @ 575-3-60

N/A 91800 BTU9.0 RLA78 LRA

Blower Motor @ 575-3-60

N/A 2 hp2.3 Unit FLA

Unit FLA @ 575-3-60

N/A 12.0

Maximum Fuse Size @ 575-3-60

N/A 20

Minimum Circuit Ampacity @ 575-3-60

N/A 14.3

Operating Power @ 575-3-60

N/A 8.41 kW

CFM

N/A 3600

Nominal Tonnage

N/A 7.6
Moisture Removal @ 82°DB / 50% R.H.1 N/A 34.1 LB/HR

Moisture Removal @ 82°DB / 60% R.H.1

N/A 43.2 LB/HR
Sensible Cooling @ 82°DB / 50% R.H.2 N/A 51.3 MBH

Sensible Cooling @ 82°DB / 60% R.H.2

N/A 45.5 MBH

Weight

N/A 900 LB

External Static Pressure

N/A 0.5 " H2O

Refrigerant

N/A R-454B (Factory Charged 45 lbs.)

Compressor Type

N/A Scroll

Filter (Quantity: 4)

N/A 16" x 20" x 1" Fiberglass

Drain Connection

N/A 1" Bar Drain
Liquid Inlet [O.D.] (up to 50')3 N/A 0.625 in

Hot Gas Outlet [O.D.] (up to 50')3

N/A 1.125 in

Note

N/A Ratings are subject to change without notice
  • 1 Reheat Mode assuming 1050 BTU/lb
  • 2 Cooling Mode with Remote Condenser at 95 °F
  • 3 Over 50 ft contact factory