Air Cooled, non water heating assist dehumidifiers are used when there is a primary pool and spa water heating source such as a hot water boiler in place.Typical applications would include, but be limited to, small pool surface area projects or in coldclimates or both.
Unit of Measure

Available Model Configurations

N/A DCA2500Y: Air Cooled DCA2500Y-CT: Water Cooled

Standard Features

N/A

- 3 Year Parts Warranty - ElectroFin Coated Coils
- Low Ambient Head Pressure Control
- Listed to UL 60335-2-40
- Powder Coated, Galvannealed Steel Cabinet
- Remote Condenser Ready
- Rifle Tube Refrigeration Coils
- Single Refrigeration Circuit
- Single Scroll Compressor
- Stainless Steel Condensate Drain Pan
- Standard Microprocessor Control System (WH Models only)
- TEFC Blower Motor

Optional Features

N/A

 - Control Options  - Defrost Timer Package  - Extended Surface Filters 2" & 4"  - External Static Upgrade  - Motorized Evaporator Bypass Damper  - Other Options Available  - Outdoor Installation Package  - Outdoor Make Up Air Assembly with Damper & Filter  - Remote Ready Delete  - Right Side Component Service Access  - Space Heating Options Available  - Top or Bottom Discharge (Not Field Convertible)  - Water Cooled Condenser for Water Heating or A/C Available

Available Voltage/Phase

N/A 208/230-1-60 208/230-3-60 460-3-60 575-3-60

Compressor @ 208/230-1-60

N/A 62300 BTU30.1 RLA170 LRA

Blower Motor @ 208/230-1-60

N/A 2.0 hp8.5 Unit FLA

Unit FLA @ 208/230-1-60

N/A 40.0

Maximum Fuse Size @ 208/230-1-60

N/A 70

Minimum Circuit Ampacity @ 208/230-1-60

N/A 47.5

Operating Power @ 208/230-1-60

N/A 6.14 kW

Compressor @ 208/230-3-60

N/A 62700 BTU

Blower Motor @ 208/230-3-60

N/A 2.0 hp6.6 Unit FLA

Unit FLA @ 208/230-3-60

N/A 29.2

Maximum Fuse Size @ 208/230-3-60

N/A 45

Minimum Circuit Ampacity @ 208/230-3-60

N/A 34.5

Operating Power @ 208/230-3-60

N/A 6.55 kW

Compressor @ 460-3-60

N/A 62700 BTU9.1 RLA74.8 LRA

Blower Motor @ 460-3-60

N/A 2.0 hp2.9 Unit FLA

Unit FLA @ 460-3-60

N/A 12.7

Maximum Fuse Size @ 460-3-60

N/A 20

Minimum Circuit Ampacity @ 460-3-60

N/A 15.0

Operating Power @ 460-3-60

N/A 6.31 kW

Compressor @ 575-3-60

N/A 62700 BTU7.7 RLA47.8 LRA

Blower Motor @ 575-3-60

N/A 2.0 hp2.3 Unit FLA

Unit FLA @ 575-3-60

N/A 10.6

Maximum Fuse Size @ 575-3-60

N/A 17.5

Minimum Circuit Ampacity @ 575-3-60

N/A 12.5

Operating Power @ 575-3-60

N/A 6.30 kW

CFM

N/A 2500

Nominal Tonnage

N/A 5.1
Moisture Removal @ 82°DB / 50% R.H.1 N/A 23.2 LB/HR

Moisture Removal @ 82°DB / 60% R.H.1

N/A 29.9 LB/HR
Sensible Cooling @ 82°DB / 50% R.H.2 N/A 37.1 MBH

Sensible Cooling @ 82°DB / 60% R.H.2

N/A 32.8 MBH

Weight

N/A 580 LB

External Static Pressure

N/A 0.5 " H2O

Refrigerant

N/A R-454B (Factory Charged 25 lbs.)

Compressor Type

N/A Scroll

Filter (Quantity: 2)

N/A 18" x 25" x 1" Fiberglass

Drain Connection

N/A 1" Bar Drain
Liquid Inlet [O.D.] (up to 50')3 N/A 0.5 in

Hot Gas Outlet [O.D.] (up to 50')3

N/A 0.875 in

Note

N/A Ratings are subject to change without notice
  • 1 Reheat Mode assuming 1050 BTU/lb
  • 2 Cooling Mode with Remote Condenser at 95 °F
  • 3 Over 50 ft contact factory