CAD (0)
  • Cart is empty
Air Cooled, non water heating assist dehumidifiers are used when there is a primary pool and spa water heating source such as a hot water boiler in place.Typical applications would include, but be limited to, small pool surface area projects or in coldclimates or both.
Unit of Measure

Available Model Configurations

N/A DCA2000Y: Air Cooled DCA2000Y-CT: Water Cooled

Standard Features

N/A

- 3 Year Parts Warranty  - ElectroFin Coated Coils  - Low Ambient Head Pressure Control  - Listed to UL 60335-2-40  - Powder Coated, Galvannealed Steel Cabinet  - Remote Condenser Ready  - Rifle Tube Refrigeration Coils  - Single Refrigeration Circuit  - Single Scroll Compressor  - Stainless Steel Condensate Drain Pan  - Standard Microprocessor Control System (WH Models only)  - TEFC Blower Motor

Optional Features

N/A

 - Control Options  - Defrost Timer Package  - Extended Surface Filters 2" & 4"  - External Static Upgrade  - Motorized Evaporator Bypass Damper  - Other Options Available  - Outdoor Installation Package  - Outdoor Make Up Air Assembly with Damper & Filter  - Remote Ready Delete  - Right Side Component Service Access  - Space Heating Options Available  - Top or Bottom Discharge (Not Field Convertible)  - Water Cooled Condenser for Water Heating or A/C Available

Available Voltage/Phase

N/A 208/230-1-60 208/230-3-60 460-3-60 575-3-60

Compressor @ 208/230-1-60

N/A 49800 BTU21.8 RLA143 LRA

Blower Motor @ 208/230-1-60

N/A 1.5 hp6.2 Unit FLA

Unit FLA @ 208/230-1-60

N/A 29.4

Maximum Fuse Size @ 208/230-1-60

N/A 50

Minimum Circuit Ampacity @ 208/230-1-60

N/A 34.9

Operating Power @ 208/230-1-60

N/A 5.04 kW

Compressor @ 208/230-3-60

N/A 49800 BTU16.0 RLA156.4 LRA

Blower Motor @ 208/230-3-60

N/A 1.5 hp4.5 Unit FLA

Unit FLA @ 208/230-3-60

N/A 21.9

Maximum Fuse Size @ 208/230-3-60

N/A 35

Minimum Circuit Ampacity @ 208/230-3-60

N/A 25.9

Operating Power @ 208/230-3-60

N/A 5.02 kW

Compressor @ 460-3-60

N/A 49800 BTU7.7 RLA69 LRA

Blower Motor @ 460-3-60

N/A 1.5 hp2.2 Unit FLA

Unit FLA @ 460-3-60

N/A 10.6

Maximum Fuse Size @ 460-3-60

N/A 17.5

Minimum Circuit Ampacity @ 460-3-60

N/A 12.5

Operating Power @ 460-3-60

N/A 4.99 kW

Compressor @ 575-3-60

N/A 49800 BTU6.4 RLA47.8 LRA

Blower Motor @ 575-3-60

N/A 1.5 hp1.9 Unit FLA

Unit FLA @ 575-3-60

N/A 8.9

Maximum Fuse Size @ 575-3-60

N/A 15

Minimum Circuit Ampacity @ 575-3-60

N/A 10.5

Operating Power @ 575-3-60

N/A 5.11 kW

CFM

N/A 2000

Nominal Tonnage

N/A 4.1
Moisture Removal @ 82°DB / 50% R.H.1 N/A 18.5 LB/HR

Moisture Removal @ 82°DB / 60% R.H.1

N/A 23.6 LB/HR
Sensible Cooling @ 82°DB / 50% R.H.2 N/A 28.6 MBH

Sensible Cooling @ 82°DB / 60% R.H.2

N/A 25.4 MBH

Weight

N/A 540 LB

External Static Pressure

N/A 0.5 " H2O

Refrigerant

N/A R-454B (Factory Charged 25 lbs.)

Compressor Type

N/A Scroll

Filter (Quantity: 2)

N/A 18" x 25" x 1" Fiberglass

Drain Connection

N/A 1" Bar Drain
Liquid Inlet [O.D.] (up to 50')3 N/A 0.5 in

Hot Gas Outlet [O.D.] (up to 50')3

N/A 0.75 in

Note

N/A Ratings are subject to change without notice
  • 1 Reheat Mode assuming 1050 BTU/lb
  • 2 Cooling Mode with Remote Condenser at 95 °F
  • 3 Over 50 ft contact factory