CAD (0)
  • Cart is empty
Air Cooled, non water heating assist dehumidifiers are used when there is a primary pool and spa water heating source such as a hot water boiler in place.Typical applications would include, but be limited to, small pool surface area projects or in coldclimates or both.
Unit of Measure

Available Model Configurations

N/A DCA1500Y: Air Cooled DCA1500Y-CT: Water Cooled

Standard Features

N/A

- 3 Year Parts Warranty - ElectroFin Coated Coils
- Low Ambient Head Pressure Control
- Listed to UL 60335-2-40
- Powder Coated, Galvannealed Steel Cabinet
- Remote Condenser Ready
- Rifle Tube Refrigeration Coils
- Single Refrigeration Circuit
- Single Scroll Compressor
- Stainless Steel Condensate Drain Pan
- Standard Microprocessor Control System (WH Models only)
- TEFC Blower Motor

Optional Features

N/A

- Control Options
- Defrost Timer Package
- Extended Surface Filters 2" & 4"
- External Static Upgrade
- Motorized Evaporator Bypass Damper
- Other Options Available
- Outdoor Installation Package
- Outdoor Make Up Air Assembly with Damper & Filter
- Remote Ready Delete
- Right Side Component Service Access
- Space Heating Options Available
- Top or Bottom Discharge (Not Field Convertible)
- Water Cooled Condenser for Water Heating or A/C Available

Available Voltage/Phase

N/A 208/230-1-60 208/230-3-60 460-3-60 575-3-60

Compressor @ 208/230-1-60

N/A 36300 BTU17.3 RLA123 LRA

Blower Motor @ 208/230-1-60

N/A 1 hp6.5 Unit FLA

Unit FLA @ 208/230-1-60

N/A 25.2

Maximum Fuse Size @ 208/230-1-60

N/A 40

Minimum Circuit Ampacity @ 208/230-1-60

N/A 29.5

Operating Power @ 208/230-1-60

N/A 3.85 kW

Compressor @ 208/230-3-60

N/A 36300 BTU12.8 RLA102.8 LRA

Blower Motor @ 208/230-3-60

N/A 1 hp3.1 Unit FLA

Unit FLA @ 208/230-3-60

N/A 17.3

Maximum Fuse Size @ 208/230-3-60

N/A 30

Minimum Circuit Ampacity @ 208/230-3-60

N/A 20.5

Operating Power @ 208/230-3-60

N/A 3.64 kW

Compressor @ 460-3-60

N/A 36300 BTU5.8 RLA50 LRA

Blower Motor @ 460-3-60

N/A 1 hp1.5 Unit FLA

Unit FLA @ 460-3-60

N/A 8.0

Maximum Fuse Size @ 460-3-60

N/A 15

Minimum Circuit Ampacity @ 460-3-60

N/A 9.5

Operating Power @ 460-3-60

N/A 3.61 kW

Compressor @ 575-3-60

N/A 36400 BTU5.1 RLA41 LRA

Blower Motor @ 575-3-60

N/A 1 hp1.2 Unit FLA

Unit FLA @ 575-3-60

N/A 6.9

Maximum Fuse Size @ 575-3-60

N/A 12

Minimum Circuit Ampacity @ 575-3-60

N/A 8.2

Operating Power @ 575-3-60

N/A 3.61 kW

CFM

N/A 1500

Nominal Tonnage

N/A 3
Moisture Removal @ 82°DB / 50% R.H.1 N/A 13.4 LB/HR

Moisture Removal @ 82°DB / 60% R.H.1

N/A 17.2 LB/HR
Sensible Cooling @ 82°DB / 50% R.H.2 N/A 20.8 MBH

Sensible Cooling @ 82°DB / 60% R.H.2

N/A 18.5 MBH

Weight

N/A 470 LB

External Static Pressure

N/A 0.5 " H2O

Refrigerant

N/A R-454B (Factory Charged 20 lbs.)

Compressor Type

N/A Scroll

Filter (Quantity: 1)

N/A 25" x 25" x 1" Fiberglass

Drain Connection

N/A 1" Bar Drain
Liquid Inlet [O.D.] (up to 50')3 N/A 0.5 in

Hot Gas Outlet [O.D.] (up to 50')3

N/A 0.75 in

Note

N/A Ratings are subject to change without notice
  • 1 Reheat Mode assuming 1050 BTU/lb
  • 2 Cooling Mode with Remote Condenser at 95 °F
  • 3 Over 50 ft contact factory