CAD (0)
  • Cart is empty
Air Cooled, non water heating assist dehumidifiers are used when there is a primary pool and spa water heating source such as a hot water boiler in place.Typical applications would include, but be limited to, small pool surface area projects or in coldclimates or both.
Unit of Measure

Available Model Configurations

N/A DCA14000Y: Air Cooled DCA14000Y-CT: Water Cooled

Standard Features

N/A

 - 3 Year Parts Warranty  - Dual Refrigeration Circuit  - Dual Scroll Compressor  - ElectroFin Coated Coils  - Low Ambient Head Pressure Control  - Listed to UL 60335-2-40  - Motorized Evaporator Bypass Damper  - Powder Coated, Galvannealed Steel Cabinet  - Remote Condenser Ready  - Rifle Tube Refrigeration Coils  - Stainless Steel Condensate Drain Pan  - Standard Microprocessor Control System (WH Models only)  - TEFC Blower Motor

Optional Features

N/A

 - Control Options  - Defrost Timer Package  - External Static Upgrade  - Other Options Available  - Outdoor Installation Package  - Outdoor Make Up Air Assembly with Damper & Filter  - Remote Ready Delete  - Right Side Component Service Access  - Space Heating Options Available  - Top or Bottom Discharge (Not Field Convertible)  - Water Cooled Condenser for Water Heating or A/C Available

Available Voltage/Phase

N/A 208/230-3-60 460-3-60 575-3-60

Compressor @ 208/230-3-60 A/B

N/A 184 / 184 MBH49 / 49 RLA386.3 /386.3 LRA

Blower Motor @ 208/230-3-60

N/A 10 hp27.0 Unit FLA

Unit FLA @ 208/230-3-60

N/A 127.4

Maximum Fuse Size @ 208/230-3-60

N/A 175

Minimum Circuit Ampacity @ 208/230-3-60

N/A 164.2

Operating Power @ 208/230-3-60

N/A 35.50 kW

Compressor @ 460-3-60 A/B

N/A 185.5 / 185.5 MBH24 / 24 RLA182 / 182 LRA

Blower Motor @ 460-3-60

N/A 10 hp12.5 Unit FLA

Unit FLA @ 460-3-60

N/A 61.6

Maximum Fuse Size @ 460-3-60

N/A 80

Minimum Circuit Ampacity @ 460-3-60

N/A 67.6

Operating Power @ 460-3-60

N/A 34.85 kW

Compressor @ 575-3-60 A/B

N/A 185.5 / 185.5 MBH19.2 / 19.2 MBH131 / 131 LRA

Blower Motor @ 575-3-60

N/A 10 hp9.8 Unit FLA

Unit FLA @ 575-3-60

N/A 49.1

Maximum Fuse Size @ 575-3-60

N/A 70

Minimum Circuit Ampacity @ 575-3-60

N/A 53.9

Operating Power @ 575-3-60

N/A 34.78 kW

CFM

N/A 14000

Nominal Tonnage

N/A 2 x 15.2 Dual Circuit
Moisture Removal @ 82°DB / 50% R.H.1 N/A 135.2 LB/HR

Moisture Removal @ 82°DB / 60% R.H.1

N/A 171.9 LB/HR
Sensible Cooling @ 82°DB / 50% R.H.2 N/A 207.1 MBH

Sensible Cooling @ 82°DB / 60% R.H.2

N/A 183.3 MBH

Weight

N/A 4000 LB

External Static Pressure

N/A 1.00 " H2O

Refrigerant

N/A R-454B (Factory Charged A/B 80 lbs.)

Compressor Type

N/A Dual Scroll

Filter (Quantity: 3)

N/A 20" x 20" x 4" Pleated

Filter (Quantity: 6)

N/A 20" x 25" x 4" Pleated

Drain Connection

N/A 1" Bar Drain

Liquid Inlet A/B [O.D.] (up to 50')

N/A 0.875 / 0.875 in

Hot Gas Outlet A/B [O.D.] (up to 50')3

N/A 1.375/1.375 in

Note

N/A Ratings are subject to change without notice
  • 1 Reheat Mode assuming 1050 BTU/lb
  • 2 Cooling Mode with Remote Condenser at 95 °F