Available Model Configurations |
N/A DCA14000Y: Air Cooled DCA14000Y-CT: Water Cooled |
Standard Features |
N/A
- 3 Year Parts Warranty - Dual Refrigeration Circuit - Dual Scroll Compressor - ElectroFin Coated Coils - Low Ambient Head Pressure Control - Listed to UL 60335-2-40 - Motorized Evaporator Bypass Damper - Powder Coated, Galvannealed Steel Cabinet - Remote Condenser Ready - Rifle Tube Refrigeration Coils - Stainless Steel Condensate Drain Pan - Standard Microprocessor Control System (WH Models only) - TEFC Blower Motor |
Optional Features |
N/A
- Control Options - Defrost Timer Package - External Static Upgrade - Other Options Available - Outdoor Installation Package - Outdoor Make Up Air Assembly with Damper & Filter - Remote Ready Delete - Right Side Component Service Access - Space Heating Options Available - Top or Bottom Discharge (Not Field Convertible) - Water Cooled Condenser for Water Heating or A/C Available |
Available Voltage/Phase |
N/A 208/230-3-60 460-3-60 575-3-60 |
Compressor @ 208/230-3-60 A/B |
N/A 184 / 184 MBH49 / 49 RLA386.3 /386.3 LRA |
Blower Motor @ 208/230-3-60 |
N/A 10 hp27.0 Unit FLA |
Unit FLA @ 208/230-3-60 |
N/A 127.4 |
Maximum Fuse Size @ 208/230-3-60 |
N/A 175 |
Minimum Circuit Ampacity @ 208/230-3-60 |
N/A 164.2 |
Operating Power @ 208/230-3-60 |
N/A 35.50 kW |
Compressor @ 460-3-60 A/B |
N/A 185.5 / 185.5 MBH24 / 24 RLA182 / 182 LRA |
Blower Motor @ 460-3-60 |
N/A 10 hp12.5 Unit FLA |
Unit FLA @ 460-3-60 |
N/A 61.6 |
Maximum Fuse Size @ 460-3-60 |
N/A 80 |
Minimum Circuit Ampacity @ 460-3-60 |
N/A 67.6 |
Operating Power @ 460-3-60 |
N/A 34.85 kW |
Compressor @ 575-3-60 A/B |
N/A 185.5 / 185.5 MBH19.2 / 19.2 MBH131 / 131 LRA |
Blower Motor @ 575-3-60 |
N/A 10 hp9.8 Unit FLA |
Unit FLA @ 575-3-60 |
N/A 49.1 |
Maximum Fuse Size @ 575-3-60 |
N/A 70 |
Minimum Circuit Ampacity @ 575-3-60 |
N/A 53.9 |
Operating Power @ 575-3-60 |
N/A 34.78 kW |
CFM |
N/A 14000 |
Nominal Tonnage |
N/A 2 x 15.2 Dual Circuit |
Moisture Removal @ 82°DB / 50% R.H.1 | N/A 135.2 LB/HR |
Moisture Removal @ 82°DB / 60% R.H.1 |
N/A 171.9 LB/HR |
Sensible Cooling @ 82°DB / 50% R.H.2 | N/A 207.1 MBH |
Sensible Cooling @ 82°DB / 60% R.H.2 |
N/A 183.3 MBH |
Weight |
N/A 4000 LB |
External Static Pressure |
N/A 1.00 " H2O |
Refrigerant |
N/A R-454B (Factory Charged A/B 80 lbs.) |
Compressor Type |
N/A Dual Scroll |
Filter (Quantity: 3) |
N/A 20" x 20" x 4" Pleated |
Filter (Quantity: 6) |
N/A 20" x 25" x 4" Pleated |
Drain Connection |
N/A 1" Bar Drain |
Liquid Inlet A/B [O.D.] (up to 50') |
N/A 0.875 / 0.875 in |
Hot Gas Outlet A/B [O.D.] (up to 50')3 |
N/A 1.375/1.375 in |
Note |
N/A Ratings are subject to change without notice |
- 1 Reheat Mode assuming 1050 BTU/lb
- 2 Cooling Mode with Remote Condenser at 95 °F