- Product Overview
- Electrical Specifications
- Design Specifications
- Pool Water Heating and Flow Data
- Water Cooled AC/Geothermal Data
- CAD / REVIT Variants
Available Model Configurations |
N/A DCA3000TVWH: Air Cooled Water Heating Assist DCA3000TVWH-CT: Water Cooled Water Heating Assist |
Standard Features |
N/A - 3 Year Parts Warranty - ElectroFin Coated Coils - Low Ambient Head Pressure Control - MET Laboratory Safety Listed to UL 1995 - Powder Coated, Galvannealed Steel Cabinet - Remote Condenser Ready - Rifle Tube Refrigeration Coils - Single Refrigeration Circuit - Single Scroll Compressor - Stainless Steel Condensate Drain Pan - Standard Microprocessor Control System (WH Models only) - TEFC High Efficiency Blower Motor |
Optional Features |
N/A - Control Options - Defrost Timer Package - Extended Surface Filters 2" & 4" - External Static Upgrade - Horizontal Discharge (Not Field Convertible) - Motorized Evaporator Bypass Damper - Other Options Available - Outdoor Make Up Air Flange Opening (Damper & Filter by Others) - Remote Ready Delete - Right Side Return Air - Space Heating Options Available - Water Cooled Condenser for Water Heating or A/C Available |
Available Voltage/Phase1 | N/A 208/230-1-60 208/230-3-60 460-3-60 575-3-60 |
N/A   |
|
Compressor @ 208/230-1-60 |
N/A 65,000 BTU28.8 RLA176 LRA |
Blower Motor @ 208/230-1-60 |
N/A 2.0 hp10 Unit FLA |
Unit FLA @ 208/230-1-60 |
N/A 40.3 |
Maximum Fuse Size @ 208/230-1-60 |
N/A 60 |
Minimum Circuit Ampacity @ 208/230-1-60 |
N/A 47.5 |
Operating Power @ 208/230-1-60 |
N/A 7.29 kW |
N/A   |
|
Compressor @ 208/230-3-60 |
N/A 65,500 BTU18.6 RLA156 LRA |
Blower Motor @ 208/230-3-60 |
N/A 2.0 hp6.0 Unit FLA |
Unit FLA @ 208/230-3-60 |
N/A 26.1 |
Maximum Fuse Size @ 208/230-3-60 |
N/A 40 |
Minimum Circuit Ampacity @ 208/230-3-60 |
N/A 30.8 |
N/A   |
|
Compressor @ 460-3-60 |
N/A 65,500 BTU9.0 RLA75 LRA |
Blower Motor @ 460-3-60 |
N/A 2.0 hp2.9 Unit FLA |
Unit FLA @ 460-3-60 |
N/A 12.7 |
Maximum Fuse Size @ 460-3-60 |
N/A 20 |
Minimum Circuit Ampacity @ 460-3-60 |
N/A 15.0 |
Operating Power @ 460-3-60 |
N/A 7.03 kW |
N/A   |
|
Compressor @ 575-3-60 |
N/A 65,500 BTU7.4 RLA54 LRA |
Blower Motor @ 575-3-60 |
N/A 2.0 hp2.3 Unit FLA |
Unit FLA @ 575-3-60 |
N/A 10.4 |
Maximum Fuse Size @ 575-3-60 |
N/A 17.5 |
Minimum Circuit Ampacity @ 575-3-60 |
N/A 12.3 |
Operating Power @ 575-3-60 |
N/A 7.01 kW |
CFM |
N/A 3000 |
Nominal Tonnage |
N/A 5.4 |
Moisture Removal @ 82°DB / 50% R.H.2 | N/A 26.1 LB/HR |
Moisture Removal @ 82°DB / 60% R.H.1 |
N/A 33.6 LB/HR |
Sensible Cooling @ 82°DB / 50% R.H.3 | N/A 38.4 MBH |
Sensible Cooling @ 82°DB / 60% R.H.2 |
N/A 34.1 MBH |
Water Flow4 | N/A 10.0 GPM |
Pressure Drop3 |
N/A 7.0 |
External Static Pressure |
N/A 0.5 " H2O |
Compressor Type |
N/A Scroll |
Filter (Quantity: 4) |
N/A 16" x 20" x 1" Fiberglass |
Drain Connection |
N/A 1" Bar Drain |
Liquid Inlet [O.D.] (up to 50')5 | N/A 0.5 in |
Hot Gas Outlet [O.D.] (up to 50')4 |
N/A 0.875 in |
Water Inlet [O.D.] |
N/A 1.125 in |
Water Outlet [O.D.] |
N/A 1.125 in |
Weight |
N/A 770 LB |
Refrigerant |
N/A R-407C (Factory Charged 25 lbs.) |
Note |
N/A Ratings are subject to change without notice |
Water Heating Capacity @ 82°DB / 50% R.H. (MBH)6 | N/A 82.0 |
Water Heating Capacity @ 82°DB / 60% R.H. (MBH)1 |
N/A 86.0 |
Water Flow (G.P.M.)7 | N/A 10.0 |
Pressure Drop2 |
N/A 7.0 |
Water Heating Capacity @ 82°DB / 50% R.H. (MBH)8 | N/A 82.0 |
Water Heating Capacity @ 82°DB / 60% R.H. (MBH)1 |
N/A 86.0 |
Water Flow (G.P.M.)9 | N/A 10.0 |
Pressure Drop2 |
N/A 7.0 |
Water Temperature Range10 | N/A 35°F to 85°F |
Available Water Sources |
N/A City Water Geothermal Loop Processed Water Water Tower |
Optional Fresh Air and Discharge Openings |
N/A
DCA3000TVWH with Optional Opening, Water Heating Assist Dehumidifier (Quote) |
- 1 380V-3Ph-50Hz Available Upon Request
- 2 Reheat Mode assuming 1050 BTU/lb
- 3 Cooling Mode with Remote Condenser at 95 °F
- 4 Water Flow data as used on 50% RH + Return Air 82 °F and Pool Water at 85 °F
- 5 Over 50 ft contact factory
- 6 Assuming 85 °F entering water temperature.
- 7 Water Flow data as used on 50% RH + Return Air 82 °F and Pool Water at 85 °F
- 8 Assuming 85 °F entering water temperature.
- 9 Water Flow data as used on 50% RH + Return Air 82 °F and Pool Water at 85 °F
- 10 Depends on a lot of factors, contact factory for details.