CAD (0)
  • Cart is empty
Pool water heating assist dehumidifiers are well suited to projects that feature large pool surface areas such as are typical in commercial applications, and are located in warm climates where the operation of the dehumidifier would spend much of its time operating in remote condenser mode providing room cooling. Typically these applications must include a primary water heating source as well.
Unit of Measure

Available Model Configurations

N/A 7000TWH-CT: Water Cooled with Pool Water Heating Assist DCA7000TWH: Air Cooled with Pool Water Heating Assist

Standard Features

N/A  - 3 Year Parts Warranty  - ElectroFin Coated Coils"  - Low Ambient Head Pressure Control  - MET Laboratory Safety Listed to UL 1995  - Motorized Evaporator Bypass Damper  - Powder Coated, Galvannealed Steel Cabinet  - Remote Condenser Ready  - Rifle Tube Refrigeration Coils  - Single Refrigeration Circuit  - Single Scroll Compressor  - Stainless Steel Condensate Drain Pan  - Standard Microprocessor Control System (WH Models only)  - TEFC Blower Motor

Optional Features

N/A  - Control Options  - Defrost Timer Package  - External Static Upgrade  - Other Options Available  - Outdoor Installation Package  - Outdoor Make Up Air Assembly with Damper & Filter  - Remote Ready Delete  - Right Side Component Service Access  - Space Heating Options Available  - Top or Bottom Discharge (Not Field Convertible)  - Water Cooled Condenser for Water Heating or A/C Available
Available Voltage/Phase1 N/A 208/230-3-60 460-3-60 575-3-60

Compressor @ 208/230-3-60

N/A 181,000 BTU53.8 RLA340 LRA

Blower Motor @ 208/230-3-60

N/A 5 hp13.7 Unit FLA

Unit FLA @ 208/230-3-60

N/A 69.2

Maximum Fuse Size @ 208/230-3-60

N/A 110

Minimum Circuit Ampacity @ 208/230-3-60

N/A 82.7

Operating Power @ 208/230-3-60

N/A 19.42 kW

N/A  

Compressor @ 460-3-60

N/A 181,000 BTU28.2 RLA173 LRA

Blower Motor @ 460-3-60

N/A 5 hp6.3 Unit FLA

Unit FLA @ 460-3-60

N/A 35.3

Maximum Fuse Size @ 460-3-60

N/A 60

Minimum Circuit Ampacity @ 460-3-60

N/A 42.4

Operating Power @ 460-3-60

N/A 19.06 kW

Available Models

N/A  

Compressor @ 575-3-60

N/A 181,000 BTU22.4 RLA132 LRA

Blower Motor @ 575-3-60

N/A 5 hp5.0 Unit FLA

Unit FLA @ 575-3-60

N/A 28.1

Maximum Fuse Size @ 575-3-60

N/A 45

Minimum Circuit Ampacity @ 575-3-60

N/A 33.7

Operating Power @ 575-3-60

N/A 19.02 kW

CFM

N/A 7000

Nominal Tonnage

N/A 15
Moisture Removal @ 82°DB / 50% R.H.2 N/A 72.0 LB/HR

Moisture Removal @ 82°DB / 60% R.H.1

N/A 92.8 LB/HR
Sensible Cooling @ 82°DB / 50% R.H.3 N/A 106.2 MBH

Sensible Cooling @ 82°DB / 60% R.H.2

N/A 94.2 MBH
Water Flow4 N/A 33/33 GPM

Pressure Drop3

N/A 11.3

Weight

N/A 1880 LB

Refrigerant

N/A R-407C (Factory Charged 80 lbs.)

External Static Pressure

N/A 0.50 " H2O

Compressor Type

N/A Scroll

Filter (Quantity: 4)

N/A 20" x 25" x 4" Pleated

Drain Connection

N/A 1" Bar Drain
Liquid Inlet [O.D.] (up to 50')5 N/A 0.875 in

Hot Gas Outlet [O.D.] (up to 50')4

N/A 1.375 in

Water Inlet [O.D.]

N/A 1.625 in

Water Outlet [O.D.]

N/A 1.625 in

Note

N/A Ratings are subject to change without notice
Water Heating Capacity @ 82°DB / 50% R.H. (MBH)6 N/A 226.5

Water Heating Capacity @ 82°DB / 60% R.H. (MBH)1

N/A 237.5
Water Flow (G.P.M.)7 N/A 34.0

Pressure Drop2

N/A 11.3
Water Heating Capacity @ 82°DB / 50% R.H. (MBH)8 N/A 226.5

Water Heating Capacity @ 82°DB / 60% R.H. (MBH)1

N/A 237.5
Water Flow (G.P.M.)9 N/A 34.0

Pressure Drop2

N/A 11.3
Water Temperature Range10 N/A 35°F to 85°F

Available Water Sources

N/A City Water Geothermal Loop Processed Water Water Tower

Optional Fresh Air and Discharge Openings

N/A , Water Heating Assist Dehumidifier (Quote)

with Indoor Hood (Indoor installation)

N/A , Water Heating Assist Dehumidifier (Quote)

with Outdoor Hood (Outdoor installation)

N/A , Water Heating Assist Dehumidifier (Quote)
  • 1 380V-3Ph-50Hz Available Upon Request
  • 2 Reheat Mode assuming 1050 BTU/lb
  • 3 Cooling Mode with Remote Condenser at 95 °F
  • 4 Water Flow data as used on 50% RH + Return Air 82 °F and Pool Water at 85 °F
  • 5 Over 50 ft contact factory
  • 6 Assuming 85 °F entering water temperature.
  • 7 Water Flow data as used on 50% RH + Return Air 82 °F and Pool Water at 85 °F
  • 8 Assuming 85 °F entering water temperature.
  • 9 Water Flow data as used on 50% RH + Return Air 82 °F and Pool Water at 85 °F
  • 10 Depends on a lot of factors, contact factory for details.