CAD (0)
  • Cart is empty
Air Cooled, non water heating assist dehumidifiers are used when there is a primary pool and spa water heating source such as a hot water boiler in place.Typical applications would include, but be limited to, small pool surface area projects or in coldclimates or both.
Unit of Measure

Available Model Configurations

N/A DCA900A: Air Cooled DCA900A-CT: Water Cooled

Standard Features

N/A  - 3 Year Parts Warranty  - ElectroFin Coated Coils"  - Low Ambient Head Pressure Control  - MET Laboratory Safety Listed to UL 1995  - Powder Coated, Galvannealed Steel Cabinet  - Remote Condenser Ready  - Rifle Tube Refrigeration Coils  - Single Refrigeration Circuit  - Single Scroll Compressor  - Stainless Steel Condensate Drain Pan  - Standard Microprocessor Control System (WH Models only)  - TEFC Blower Motor

Optional Features

N/A  - Control Options  - Defrost Timer Package  - ExtendedSurface Filters 2" & 4"  - External Static Upgrade  - Motorized Evaporator Bypass Damper  - Other Options Available  - Outdoor Installation Package  - Outdoor Make Up Air Assembly with Damper & Filter  - Remote Ready Delete  - Right Side Component Service Access  - Space Heating Options Available  - Top or Bottom Discharge (Not Field Convertible)  - Water Cooled Condenser for Water Heating or A/C Available

Available Voltage/Phase

N/A 208/230-1-60 208/230-3-60 460-3-60

Compressor @ 208/230-1-60

N/A 24000 BTU12.8 RLA64 LRA

Blower Motor @ 208/230-1-60

N/A 0.5 hp4.4 Unit FLA

Unit FLA @ 208/230-1-60

N/A 18.6

Maximum Fuse Size @ 208/230-1-60

N/A 30

Minimum Circuit Ampacity @ 208/230-1-60

N/A 21.8

Operating Power @ 208/230-1-60

N/A 2.71 kW

Compressor @ 208/230-3-60

N/A 24000 BTU8.3 RLA58 LRA

Blower Motor @ 208/230-3-60

N/A 0.5 hp2.0 Unit FLA

Unit FLA @ 208/230-3-60

N/A 11.7

Maximum Fuse Size @ 208/230-3-60

N/A 17.5

Minimum Circuit Ampacity @ 208/230-3-60

N/A 13.8

Operating Power @ 208/230-3-60

N/A 2.63 kW

Compressor @ 460-3-60

N/A 24000 BTU5.1 RLA28 LRA

Blower Motor @ 460-3-60

N/A 0.5 hp1.0 Unit FLA

Unit FLA @ 460-3-60

N/A 6.8

Maximum Fuse Size @ 460-3-60

N/A 12

Minimum Circuit Ampacity @ 460-3-60

N/A 8.1

Operating Power @ 460-3-60

N/A 2.63 kW

CFM

N/A 950

Nominal Tonnage

N/A 2
Moisture Removal @ 82°DB / 50% R.H.1 N/A 9.2 LB/HR

Moisture Removal @ 82°DB / 60% R.H.1

N/A 11.8 LB/HR
Sensible Cooling @ 82°DB / 50% R.H.2 N/A 13.8 MBH

Sensible Cooling @ 82°DB / 60% R.H.2

N/A 12.2 MBH

Weight

N/A 420 LB

External Static Pressure

N/A 0.50 " H2O

Refrigerant

N/A R-410A (Factory Charged 18 lbs.)

Compressor Type

N/A Scroll

Filter (Quantity: 1)

N/A 25" x 25" x 1" Fiberglass

Drain Connection

N/A 1" Bar Drain
Liquid Inlet [O.D.] (up to 50')3 N/A 0.375 in

Hot Gas Outlet [O.D.] (up to 50')3

N/A 0.625 in

Note

N/A Ratings are subject to change without notice

Optional Fresh Air and Discharge Openings

N/A , Non Water Heating Assist Dehumidifier (Quote)

with Indoor Hood (Indoor installation)

N/A , Non Water Heating Assist Dehumidifier (Quote)

with Outdoor Hood (Outdoor installation)

N/A , Non Water Heating Assist Dehumidifier (Quote)
  • 1 Reheat Mode assuming 1050 BTU/lb
  • 2 Cooling Mode with Remote Condenser at 95 °F
  • 3 Over 50 ft contact factory