CAD (0)
  • Cart is empty
Air Cooled, non water heating assist dehumidifiers are used when there is a primary pool and spa water heating source such as a hot water boiler in place.Typical applications would include, but be limited to, small pool surface area projects or in coldclimates or both.
Unit of Measure

Available Model Configurations

N/A DCA3000T: Air Cooled DCA3000T-CT: Water Cooled

Standard Features

N/A  - 3 Year Parts Warranty  - ElectroFin Coated Coils"  - Low Ambient Head Pressure Control  - MET Laboratory Safety Listed to UL 1995  - Powder Coated, Galvannealed Steel Cabinet  - Remote Condenser Ready  - Rifle Tube Refrigeration Coils  - Single Refrigeration Circuit  - Single Scroll Compressor  - Stainless Steel Condensate Drain Pan  - Standard Microprocessor Control System (WH Models only)  - TEFC Blower Motor

Optional Features

N/A  - Control Options  - Defrost Timer Package  - ExtendedSurface Filters 2" & 4"  - External Static Upgrade  - Motorized Evaporator Bypass Damper  - Other Options Available  - Outdoor Installation Package  - Outdoor Make Up Air Assembly with Damper & Filter  - Remote Ready Delete  - Right Side Component Service Access  - Space Heating Options Available  - Top or Bottom Discharge (Not Field Convertible)  - Water Cooled Condenser for Water Heating or A/C Available

Available Voltage/Phase

N/A 208/230-1-60 208/230-3-60 460-3-60 575-3-60

N/A  

Compressor @ 208/230-1-60

N/A 65,000 BTU28.8 RLA176 LRA

Blower Motor @ 208/230-1-60

N/A 1.5 hp7.7 Unit FLA

Unit FLA @ 208/230-1-60

N/A 36.8

Maximum Fuse Size @ 208/230-1-60

N/A 60

Minimum Circuit Ampacity @ 208/230-1-60

N/A 44.0

Operating Power @ 208/230-1-60

N/A 6.8 kW

N/A  

Compressor @ 208/230-3-60

N/A 65,500 BTU18.6 RLA156 LRA

Blower Motor @ 208/230-3-60

N/A 1.5 hp4.8 Unit FLA

Unit FLA @ 208/230-3-60

N/A 24.9

Maximum Fuse Size @ 208/230-3-60

N/A 40

Minimum Circuit Ampacity @ 208/230-3-60

N/A 29.6

Operating Power @ 208/230-3-60

N/A 6.72 kW

N/A  

Compressor @ 460-3-60

N/A 65,500 BTU9.0 RLA75 LRA

Blower Motor @ 460-3-60

N/A 1.5 hp2.4 Unit FLA

Unit FLA @ 460-3-60

N/A 12.2

Maximum Fuse Size @ 460-3-60

N/A 20

Minimum Circuit Ampacity @ 460-3-60

N/A 14.5

Operating Power @ 460-3-60

N/A 6.72 kW

N/A  

Compressor @ 575-3-60

N/A 65,500 BTU7.4 RLA54 LRA

Blower Motor @ 575-3-60

N/A 1.5 hp1.9 Unit FLA

Unit FLA @ 575-3-60

N/A 10.0

Maximum Fuse Size @ 575-3-60

N/A 15

Minimum Circuit Ampacity @ 575-3-60

N/A 11.9

Operating Power @ 575-3-60

N/A 6.56 kW

CFM

N/A 3000

Nominal Tonnage

N/A 5.4
Moisture Removal @ 82°DB / 50% R.H.1 N/A 26.1 LB/HR

Moisture Removal @ 82°DB / 60% R.H.1

N/A 33.6 LB/HR
Sensible Cooling @ 82°DB / 50% R.H.2 N/A 38.4 MBH

Sensible Cooling @ 82°DB / 60% R.H.2

N/A 34.1 MBH

Weight

N/A 750 LB

External Static Pressure

N/A 0.50 " H2O

Refrigerant

N/A R-407C (Factory Charged 25 lbs.)

Compressor Type

N/A Scroll

Drain Connection

N/A 1" Bar Drain
Liquid Inlet [O.D.] (up to 50')3 N/A 0.5 in

Hot Gas Outlet [O.D.] (up to 50')3

N/A 0.875 in

Note

N/A Ratings are subject to change without notice

Optional Fresh Air and Discharge Openings

N/A , Non Water Heating Assist Dehumidifier (Quote)

with Indoor Hood (Indoor installation)

N/A , Non Water Heating Assist Dehumidifier (Quote)

with Outdoor Hood (Outdoor installation)

N/A , Non Water Heating Assist Dehumidifier (Quote)
  • 1 Reheat Mode assuming 1050 BTU/lb
  • 2 Cooling Mode with Remote Condenser at 95 °F
  • 3 Over 50 ft contact factory