CAD (0)
  • Cart is empty
Air Cooled, non water heating assist dehumidifiers are used when there is a primary pool and spa water heating source such as a hot water boiler in place. Typical applications would include, but be limited to, small pool surface area projects or in cold climates or both.
Unit of Measure

Available Model Configurations

N/A DCA2000AV: Air Cooled DCA2000AV-CT: Water Cooled

Standard Features

N/A - 3 Year Parts Warranty - ElectroFin Coated Coils - Low Ambient Head Pressure Control - MET Laboratory Safety Listed to UL 1995 - Powder Coated, Galvannealed Steel Cabinet - Remote Condenser Ready - Rifle Tube Refrigeration Coils - Single Refrigeration Circuit - Single Scroll Compressor - Stainless Steel Condensate Drain Pan - Standard Microprocessor Control System (WH Models only) - TEFC High Efficiency Blower Motor

Optional Features

N/A - Control Options - Defrost Timer Package - Extended Surface Filters 2" & 4" - External Static Upgrade - Horizontal Discharge (Not Field Convertible) - Motorized Evaporator Bypass Damper - Other Options Available - Outdoor Make Up Air Flange Opening (Damper & Filter by Others) - Remote Ready Delete - Right Side Return Air - Space Heating Options Available - Water Cooled Condenser for Water Heating or A/C Available
Available Voltage/Phase1 N/A 208/230-1-60 208/230-3-60 460-3-60 575-3-60

Compressor @ 208/230-1-60

N/A 49400 BTU25.0 RLA134 LRA

Blower Motor @ 208/230-1-60

N/A 1.5 hp6.5 Unit FLA

Unit FLA @ 208/230-1-60

N/A 32.9

Maximum Fuse Size @ 208/230-1-60

N/A 60

Minimum Circuit Ampacity @ 208/230-1-60

N/A 39.2

Operating Power @ 208/230-1-60

N/A 5.18 kW

Compressor @ 208/230-3-60

N/A 49700 BTU15.9 RLA110 LRA

Blower Motor @ 208/230-3-60

N/A 1.5 hp4.8 Unit FLA

Unit FLA @ 208/230-3-60

N/A 22.1

Maximum Fuse Size @ 208/230-3-60

N/A 35

Minimum Circuit Ampacity @ 208/230-3-60

N/A 26.1

Operating Power @ 208/230-3-60

N/A 5.24 kW

Compressor @ 460-3-60

N/A 50000 BTU7.1 RLA52 LRA

Blower Motor @ 460-3-60

N/A 1.5 hp2.4 Unit FLA

Unit FLA @ 460-3-60

N/A 10.2

Maximum Fuse Size @ 460-3-60

N/A 17.5

Minimum Circuit Ampacity @ 460-3-60

N/A 12.0

Operating Power @ 460-3-60

N/A 5.22 kW

N/A  

Compressor @ 575-3-60

N/A 49700 BTU5.1 RLA39.5 LRA

Blower Motor @ 575-3-60

N/A 1.5 hp1.9 Unit FLA

Unit FLA @ 575-3-60

N/A 7.6

Maximum Fuse Size @ 575-3-60

N/A 12

Minimum Circuit Ampacity @ 575-3-60

N/A 8.9

Operating Power @ 575-3-60

N/A 5.06 kW

CFM

N/A 2000

Nominal Tonnage

N/A 4.1
Moisture Removal @ 82°DB / 50% R.H.2 N/A 18.9 LB/HR

Moisture Removal @ 82°DB / 60% R.H.1

N/A 24.3 LB/HR
Sensible Cooling @ 82°DB / 50% R.H.3 N/A 28.2 MBH

Sensible Cooling @ 82°DB / 60% R.H.2

N/A 25.1 MBH

Weight

N/A 660 LB

External Static Pressure

N/A 0.50 " H2O

Refrigerant

N/A R-410A (Factory Charged 25 lbs.)

Compressor Type

N/A Scroll

Filter (Quantity: 2)

N/A 18" x 25" x 1" Fiberglass

Drain Connection

N/A 1" Bar Drain
Liquid Inlet [O.D.] (up to 50')4 N/A 0.5 in

Hot Gas Outlet [O.D.] (up to 50')3

N/A 0.75 in

Note

N/A Ratings are subject to change without notice

Optional Fresh Air and Discharge Openings

N/A , Air Cooled - Non Water Heating Dehumidifier (Quote)
  • 1 380V-3Ph-50Hz Available Upon Request
  • 2 Reheat Mode assuming 1050 BTU/lb
  • 3 Cooling Mode with Remote Condenser at 95 °F
  • 4 Over 50 ft contact factory