Air Cooled, non water heating assist dehumidifiers are used when there is a primary pool and spa water heating source such as a hot water boiler in place. Typical applications would include, but be limited to, small pool surface area projects or in cold climates or both.
Unit of Measure
Available Model Configurations |
N/A DCA1500AV: Air Cooled DCA1500AV-CT: Water Cooled |
Standard Features |
N/A - 3 Year Parts Warranty - ElectroFin Coated Coils - Low Ambient Head Pressure Control - MET Laboratory Safety Listed to UL 1995 - Powder Coated, Galvannealed Steel Cabinet - Remote Condenser Ready - Rifle Tube Refrigeration Coils - Single Refrigeration Circuit - Single Scroll Compressor - Stainless Steel Condensate Drain Pan - Standard Microprocessor Control System (WH Models only) - TEFC High Efficiency Blower Motor |
Optional Features |
N/A - Control Options - Defrost Timer Package - Extended Surface Filters 2" & 4" - External Static Upgrade - Horizontal Discharge (Not Field Convertible) - Motorized Evaporator Bypass Damper - Other Options Available - Outdoor Make Up Air Flange Opening (Damper & Filter by Others) - Remote Ready Delete - Right Side Return Air - Space Heating Options Available - Water Cooled Condenser for Water Heating or A/C Available |
Available Voltage/Phase1 | N/A 208/230-1-60 208/230-3-60 460-3-60 575-3-60 |
Compressor @ 208/230-1-60 |
N/A 36000 BTU17.9 RLA112 LRA |
Blower Motor @ 208/230-1-60 |
N/A 1.0 hp6.4 Unit FLA |
Unit FLA @ 208/230-1-60 |
N/A 25.7 |
Maximum Fuse Size @ 208/230-1-60 |
N/A 40 |
Minimum Circuit Ampacity @ 208/230-1-60 |
N/A 30.2 |
Operating Power @ 208/230-1-60 |
N/A 3.89 kW |
Compressor @ 208/230-3-60 |
N/A 36000 BTU13.5 RLA88 LRA |
Blower Motor @ 208/230-3-60 |
N/A 1 hp3.2 Unit FLA |
Unit FLA @ 208/230-3-60 |
N/A 18.1 |
Maximum Fuse Size @ 208/230-3-60 |
N/A 30 |
Minimum Circuit Ampacity @ 208/230-3-60 |
N/A 21.5 |
Operating Power @ 208/230-3-60 |
N/A 3.88 kW |
Compressor @ 460-3-60 |
N/A 36000 BTU6.0 RLA44 LRA |
Blower Motor @ 460-3-60 |
N/A 1 hp1.6 Unit FLA |
Unit FLA @ 460-3-60 |
N/A 8.3 |
Maximum Fuse Size @ 460-3-60 |
N/A 15 |
Minimum Circuit Ampacity @ 460-3-60 |
N/A 9.8 |
Operating Power @ 460-3-60 |
N/A 3.79 kW |
N/A   |
|
Compressor @ 575-3-60 |
N/A 36000 BTU4.9 RLA34 LRA |
Blower Motor @ 575-3-60 |
N/A 1 hp1.5 Unit FLA |
Unit FLA @ 575-3-60 |
N/A 7.0 |
Maximum Fuse Size @ 575-3-60 |
N/A 12 |
Minimum Circuit Ampacity @ 575-3-60 |
N/A 8.2 |
Operating Power @ 575-3-60 |
N/A 3.90 kW |
CFM |
N/A 1500 |
Nominal Tonnage |
N/A 3 |
Moisture Removal @ 82°DB / 50% R.H.2 | N/A 13.9 LB/HR |
Moisture Removal @ 82°DB / 60% R.H.1 |
N/A 17.8 LB/HR |
Sensible Cooling @ 82°DB / 50% R.H.3 | N/A 20.6 MBH |
Sensible Cooling @ 82°DB / 60% R.H.2 |
N/A 18.2 MBH |
Weight |
N/A 585 LB |
External Static Pressure |
N/A 0.50 " H2O |
Refrigerant |
N/A R-410A (Factory Charged 20 lbs.) |
Compressor Type |
N/A Scroll |
Filter (Quantity: 2) |
N/A 18" x 25" x 1" Fiberglass |
Drain Connection |
N/A 1" Bar Drain |
Liquid Inlet [O.D.] (up to 50')4 | N/A 0.5 in |
Hot Gas Outlet [O.D.] (up to 50')3 |
N/A 0.75 in |
Note |
N/A Ratings are subject to change without notice |
Optional Fresh Air and Discharge Openings |
N/A
DCA1500AV with Optional Opening, Air Cooled - Non Water Heating Dehumidifier (Quote) |
- 1 380V-3Ph-50Hz Available Upon Request
- 2 Reheat Mode assuming 1050 BTU/lb
- 3 Cooling Mode with Remote Condenser at 95 °F
- 4 Over 50 ft contact factory