CAD (0)
  • Cart is empty
DCA EDHS series duct heaters will provide additional or can be a primary source of room space heating.

EDHS series duct heaters are for mounting downstream fromthe discharge of the dehumidifier only. They are shipped loose forfield installation. A single high voltage source separate from thedehumidifier and a single low voltage connection are all this isrequired - allowing for easy installation.

Standard with every heater are air flow switches, high limit controlsand fuse blocks. The optional two-stage room thermostat ties inwith the 24 volt circuitry of any DCA dehumidifier. DCA also offersa complete line of gas fired duct in-line duct furnaces when desired.
Unit of Measure

Dehumidifier Model #s

N/A DCA4800A/AWH DCA4800T/TWH

Add on Electric Heating Capacity

N/A 40 kW136,560 BTUH

Stages

N/A 2

Duct Dimensions W x H

N/A 28 x 19 in

Standard Features

N/A
  • Magnetic Contactors
  • Automatic High Limit Switch
  • Airflow Pressure Switch
  • 24V Transformer
  • Pilot Relay
  • Staging as required for each 47 Amp Circuit
  • Time Delay between stages
  • Single Point Power Connection to Terminal Block
  • Low Voltage Terminal Strip
  • Grounding Lug
  • Welding Construction using 20 MSG Galvanized Steel
  • Hinged Cover
  • Wiring Diagram
  • Fused Circuits per N.E.C., U.L. and CSA
  • ETL Listed (build to Conform to U.L. and N.E.C. requirements)
  • Straight Flange to fit Unit Discharge
  • Grade AA Chromel Corrosion resistant element (For use with corrosive environments such as indoor swimming pool enclosures, chemical plants and water/wastewater treatment facilities.)

Optional Features

N/A
  • Slip in Duct Heaters available
  • Downflow Duct Heaters available (in EDHS Only)
  • Slip In Duct, Finned Tubular Heaters also available - Contact Factory
  • SCR Control Available
  • Additional Stages Available - Consult Factory
  • Outdoor Heaters Available

Note

N/A Ratings are subject to change without notice

208V/3 Phase

N/A Current Draw: 111.03 MCA: 138.79 MOCP: 166.55

460V/3 Phase

N/A Current Draw: 50.21 MCA: 62.76 MOCP: 75.31

Electrical Specifications Note

N/A
  1. Control Voltage for above -24 volts
  2. Above specifications for all DCA series Air-Cooled & Water-Cooled units
  3. Any voltage desire, that is not listed, please contact factory.
Diagram1 N/A
EDHS Series Electric Duct Heater Diagram

A

N/A 16.75 in

B

N/A 26.75 in

C

N/A 7 (208V-3ph), 5 (460V-3ph) in

D

N/A 60 (208V-3ph), 30 (460V-3ph) in

E

N/A 19 in

F

N/A 7 in

G

N/A 4 in
  • 1 Dimensions are subject to change without notice