CAD (0)
▾
DCA EDHS series duct heaters will provide additional or can be a primary source of room space heating. EDHS series duct heaters are for mounting downstream fromthe discharge of the dehumidifier only. They are shipped loose forfield installation. A single high voltage source separate from thedehumidifier and a single low voltage connection are all this isrequired - allowing for easy installation.Standard with every heater are air flow switches, high limit controlsand fuse blocks. The optional two-stage room thermostat ties inwith the 24 volt circuitry of any DCA dehumidifier. DCA also offersa complete line of gas fired duct in-line duct furnaces when desired.
Unit of Measure
Dehumidifier Model #s |
N/A DCA3600A/AWH DCA3600T/TWH |
Add on Electric Heating Capacity |
N/A 30 kW102,420 BTUH |
Stages |
N/A 2 |
Duct Dimensions W x H |
N/A 25 x 18 in |
Standard Features |
N/A
|
Optional Features |
N/A
|
Note |
N/A Ratings are subject to change without notice |
208V/3 Phase |
N/A Current Draw: 83.27 MCA: 104.09 MOCP: 124.91 |
460V/3 Phase |
N/A Current Draw: 37.65 MCA: 47.07 MOCP: 56.48 |
Electrical Specifications Note |
N/A
|
- 1 Dimensions are subject to change without notice