CAD (0)
▾
Power Exhausted (HFP)
The outdoor gas duct furnace was design to be the primary
heating source for a building and is certified for, non residential,
commercial applications only. These furnaces are power vented
eliminating any effect of an erratic chimney. Available in 11
models sizes from 75.000 to 400,000 btu/hr for either natural or
propane gas operation.
The airflow direction can be specified when ordering the unit.
This duct furnace is certified for location downstream from the
dehumidifier and has holes to drain any condensate that may flow
onto the roof. There are many other options available including
various types of gas control valves to suit specific requirements.
Unit of Measure
Standard Features |
N/A - 18 gauge aluminized steel cabinet with a baked-on polyester powder paint finish on exterior casing parts - 409 stainless steel drip pan - 409 stainless steel heat exchanger and burners - All units a minimum of 80% thermally efficient - C.S.A. certification for use in the US and Canada - Certified to 3.0" W.C. external static pressure - Combination combustion air/exhaust vent cap - ETL certification - High limit safety control - Left side (when looking into the discharge) access to burner and gas controls with slide-out burner drawer - Natural gas input - Power exhaust - Rail type mounting base for slab installation - Separate line voltage and low voltage terminal strips - Side or bottom gas connection access - Single 115V control step down transformer with 24V gas control circuit - Single stage intermittent pilot with continuous retry control system for operation on natural gas. - Two-stage gas valve |
Optional Features |
N/A - Adjustable differential air flow proving system - Building management compatible gas controls for modulation control using a 0-10 VDC or 4-20 mA input - Control relay - double pole, double throw - Control step down transformers for 208/230V/1Ph and 208/230/460/575V/3Ph - Fan delay timer - High and/or low gas pressure switches - Manual reset high limit switch - Mechanical modulation and electronic modulation controls for natural gas - Multiple furnace electronic amplifier for controlling up to 4 duct furnaces with one discharge air sensor - Right side access to burner and gas controls - Single stage intermittent pilot with lockout control system for operation on propane gas - Supply air fire stat - Timed freeze protection - Two-stage, mechanical modulation, and electronic modulation controls for propane gas |
Gas Connection Pipe Size |
N/A 1/2 in |
Approximate Unit Shipping Weight |
N/A 343 lb |
Approximate Unit Net Weight |
N/A 258 lb |
Btu/Hr Input |
N/A 150,000 |
Btu/Hr Output |
N/A 120,000 |
20°F Air Temperature Rise |
N/A 5556 CFM |
25°F Air Temperature Rise |
N/A 4444 CFM |
30°F Air Temperature Rise |
N/A 3704 CFM |
35°F Air Temperature Rise |
N/A 3175 CFM |
40°F Air Temperature Rise |
N/A 2778 CFM |
45°F Air Temperature Rise |
N/A 2469 CFM |
50°F Air Temperature Rise |
N/A 2222 CFM |
55°F Air Temperature Rise |
N/A 2020 CFM |
60°F Air Temperature Rise |
N/A 1852 CFM |
Air Temperature and External Static Pressure Limits |
N/A The maximum allowable discharge air temperature is 150ºF. The maximum allowable air temperature rise for Low Air Temperature Rise Outdoor Units is 60ºF. The maximum allowable air temperature rise for High Air Temperature Rise Outdoor Units is 100ºF. All duct furnaces are designed for a maximum allowable static pressure of 3.0" W.C. on the heat exchanger. |
Note |
N/A
|
115/60/1 Supply Voltage |
N/A 1.40 A |
Total Unit Amp Draw |
N/A The total unit amp draw is a combination of the control step down transformer and the power exhauster motor. The control step down transformer includes damper actuators, ignition controllers, gas valves, control relays, amplifiers, and motor starters. |
- 1 Dimensions are subject to change without notice