CAD (0)
  • Cart is empty
Air Cooled, non water heating assist dehumidifiers are used when there is a primary pool and spa water heating source such as a hot water boiler in place. Typical applications would include, but be limited to, small pool surface area projects or in cold climates or both.
Unit of Measure

Available Model Configurations

N/A DCA1500TV: Air Cooled DCA1500TV-CT: Water Cooled

Standard Features

N/A - 3 Year Parts Warranty - ElectroFin Coated Coils - Low Ambient Head Pressure Control - MET Laboratory Safety Listed to UL 1995 - Powder Coated, Galvannealed Steel Cabinet - Remote Condenser Ready - Rifle Tube Refrigeration Coils - Single Refrigeration Circuit - Single Scroll Compressor - Stainless Steel Condensate Drain Pan - Standard Microprocessor Control System (WH Models only) - TEFC High Efficiency Blower Motor

Optional Features

N/A - Control Options - Defrost Timer Package - Extended Surface Filters 2" & 4" - External Static Upgrade - Horizontal Discharge (Not Field Convertible) - Motorized Evaporator Bypass Damper - Other Options Available - Outdoor Make Up Air Flange Opening (Damper & Filter by Others) - Remote Ready Delete - Right Side Return Air - Space Heating Options Available - Water Cooled Condenser for Water Heating or A/C Available
Available Voltage/Phase1 N/A 208/230-1-60 208/230-3-60 460-3-60 575-3-60

N/A  

Compressor @ 208/230-1-60

N/A 36,600 BTU19.2 RLA112 LRA

Blower Motor @ 208/230-1-60

N/A 1 hp6.4 Unit FLA

Unit FLA @ 208/230-1-60

N/A 27.0

Maximum Fuse Size @ 208/230-1-60

N/A 40

Minimum Circuit Ampacity @ 208/230-1-60

N/A 31.8

Operating Power @ 208/230-1-60

N/A 4.11 kW

N/A  

Compressor @ 208/230-3-60

N/A 36,900 BTU12.2 RLA93 LRA

Blower Motor @ 208/230-3-60

N/A 1 hp3.2 Unit FLA

Unit FLA @ 208/230-3-60

N/A 16.8

Maximum Fuse Size @ 208/230-3-60

N/A 25

Minimum Circuit Ampacity @ 208/230-3-60

N/A 19.9

Operating Power @ 208/230-3-60

N/A 4.05 kW

N/A  

Compressor @ 460-3-60

N/A 36,900 BTU5.8 RLA48 LRA

Blower Motor @ 460-3-60

N/A 1 hp1.6 Unit FLA

Unit FLA @ 460-3-60

N/A 8.1

Maximum Fuse Size @ 460-3-60

N/A 12

Minimum Circuit Ampacity @ 460-3-60

N/A 9.6

Operating Power @ 460-3-60

N/A 3.98 kW

N/A  

Compressor @ 575-3-60

N/A 36,900 BTU4.4 RLA33 LRA

Blower Motor @ 575-3-60

N/A 1 hp1.5 Unit FLA

Unit FLA @ 575-3-60

N/A 6.5

Maximum Fuse Size @ 575-3-60

N/A 10

Minimum Circuit Ampacity @ 575-3-60

N/A 7.6

Operating Power @ 575-3-60

N/A 4.04 kW

CFM

N/A 1500

Nominal Tonnage

N/A 3
Moisture Removal @ 82°DB / 50% R.H.2 N/A 14.7 LB/HR

Moisture Removal @ 82°DB / 60% R.H.1

N/A 18.9 LB/HR
Sensible Cooling @ 82°DB / 50% R.H.3 N/A 21.6 MBH

Sensible Cooling @ 82°DB / 60% R.H.2

N/A 19.2 MBH

Weight

N/A 585 LB

External Static Pressure

N/A 0.50 " H2O

Refrigerant

N/A R-407C (Factory Charged 20 lbs.)

Compressor Type

N/A Scroll

Filter (Quantity: 2)

N/A 18" x 25" x 1" Fiberglass

Drain Connection

N/A 1" Bar Drain
Liquid Inlet [O.D.] (up to 50')4 N/A 0.5 in

Hot Gas Outlet [O.D.] (up to 50')3

N/A 0.75 in

Note

N/A Ratings are subject to change without notice

Optional Fresh Air and Discharge Openings

N/A , Air Cooled - Non Water Heating Dehumidifier (Quote)
  • 1 380V-3Ph-50Hz Available Upon Request
  • 2 Reheat Mode assuming 1050 BTU/lb
  • 3 Cooling Mode with Remote Condenser at 95 °F
  • 4 Over 50 ft contact factory