CAD (0)
  • Cart is empty
Air Cooled, non water heating assist dehumidifiers are used when there is a primary pool and spa water heating source such as a hot water boiler in place. Typical applications would include, but be limited to, small pool surface area projects or in cold climates or both.
Unit of Measure

Available Model Configurations

N/A DCA900TV: Air Cooled DCA900TV-CT: Water Cooled

Standard Features

N/A  - 3 Year Parts Warranty  - ElectroFin Coated Coils  - Low Ambient Head Pressure Control  - MET Laboratory Safety Listed to UL 1995  - Powder Coated, Galvannealed Steel Cabinet  - Remote Condenser Ready  - Rifle Tube Refrigeration Coils  - Single Refrigeration Circuit  - Single Scroll Compressor  - Stainless Steel Condensate Drain Pan  - Standard Microprocessor Control System (WH Models only)  - TEFC High Efficiency Blower Motor

Optional Features

N/A  - Control Options  - Defrost Timer Package  - Extended Surface Filters 2" & 4"  - External Static Upgrade  - Horizontal Discharge (Not Field Convertible)  - Motorized Evaporator Bypass Damper  - Other Options Available  - Outdoor Make Up Air Flange Opening (Damper & Filter by Others)  - Remote Ready Delete  - Right Side Return Air  - Space Heating Options Available  - Water Cooled Condenser for Water Heating or A/C Available
Available Voltage/Phase1 N/A 208/230-1-60 208/230-3-60 460-3-60

N/A  

Compressor @ 208/230-1-60

N/A 24,300 BTU13.5 RLA68 LRA

Blower Motor @ 208/230-1-60

N/A 0.5 hp4.4 Unit FLA

Unit FLA @ 208/230-1-60

N/A 19.3

Maximum Fuse Size @ 208/230-1-60

N/A 30

Minimum Circuit Ampacity @ 208/230-1-60

N/A 22.7

Operating Power @ 208/230-1-60

N/A 2.77 kW

N/A  

Compressor @ 208/230-3-60

N/A 24,400 BTU8.0 RLA58 LRA

Blower Motor @ 208/230-3-60

N/A 0.5 hp2.0 Unit FLA

Unit FLA @ 208/230-3-60

N/A 11.4

Maximum Fuse Size @ 208/230-3-60

N/A 17.5

Minimum Circuit Ampacity @ 208/230-3-60

N/A 13.4

Operating Power @ 208/230-3-60

N/A 2.69 kW

N/A  

Compressor @ 460-3-60

N/A 24,400 BTU4.2 RLA29 LRA

Blower Motor @ 460-3-60

N/A 0.5 hp1.0 Unit FLA

Unit FLA @ 460-3-60

N/A 5.9

Maximum Fuse Size @ 460-3-60

N/A 10

Minimum Circuit Ampacity @ 460-3-60

N/A 7.0

Operating Power @ 460-3-60

N/A 2.69 kW

CFM

N/A 950

Nominal Tonnage

N/A 2
Moisture Removal @ 82°DB / 50% R.H.2 N/A 9.7 LB/HR

Moisture Removal @ 82°DB / 60% R.H.1

N/A 12.5 LB/HR
Sensible Cooling @ 82°DB / 50% R.H.3 N/A 14.3 MBH

Sensible Cooling @ 82°DB / 60% R.H.2

N/A 12.7 MBH

Weight

N/A 570 LB

External Static Pressure

N/A 0.50 " H2O

Refrigerant

N/A R-407C (Factory Charged 18 lbs.)

Compressor Type

N/A Scroll

Filter (Quantity: 2)

N/A 18" x 25" x 1" Fiberglass

Drain Connection

N/A 1" Bar Drain
Liquid Inlet [O.D.] (up to 50')4 N/A 0.375 in

Hot Gas Outlet [O.D.] (up to 50')3

N/A 0.625 in

Note

N/A Ratings are subject to change without notice

Optional Fresh Air and Discharge Openings

N/A , Air Cooled - Non Water Heating Dehumidifier (Quote)
  • 1 380V-3Ph-50Hz Available Upon Request
  • 2 Reheat Mode assuming 1050 BTU/lb
  • 3 Cooling Mode with Remote Condenser at 95 °F
  • 4 Over 50 ft contact factory