Available Model Configurations |
N/A 3300AWH-CT: Water Cooled with Pool Water Heating Assist DCA3300AWH: Air Cooled with Pool Water Heating Assist |
Standard Features |
N/A - 3 Year Parts Warranty - ElectroFin Coated Coils" - Low Ambient Head Pressure Control - MET Laboratory Safety Listed to UL 1995 - Motorized Evaporator Bypass Damper (WH Models Only) - Powder Coated, Galvannealed Steel Cabinet - Remote Condenser Ready - Rifle Tube Refrigeration Coils - Single Refrigeration Circuit - Single Scroll Compressor - Stainless Steel Condensate Drain Pan - Standard Microprocessor Control System (WH Models only) - TEFC Blower Motor |
Optional Features |
N/A - Control Options - Defrost Timer Package - ExtendedSurface Filters 2" & 4" - External Static Upgrade - Other Options Available - Outdoor Installation Package - Outdoor Make Up Air Assembly with Damper & Filter - Remote Ready Delete - Right Side Component Service Access - Space Heating Options Available - Top or Bottom Discharge (Not Field Convertible) - Water Cooled Condenser for Water Heating or A/C Available |
Available Voltage/Phase1 | N/A 208/230-1-60 208/230-3-60 460-3-60 575-3-60 |
Compressor @ 208/230-1-60 |
N/A 82500 BTU32.1 RLA185 LRA |
Blower Motor @ 208/230-1-60 |
N/A 2 hp10 Unit FLA |
Unit FLA @ 208/230-1-60 |
N/A 43.6 |
Maximum Fuse Size @ 208/230-1-60 |
N/A 70 |
Minimum Circuit Ampacity @ 208/230-1-60 |
N/A 51.7 |
Operating Power @ 208/230-1-60 |
N/A 8.33 kW |
Compressor @ 208/230-3-60 |
N/A 83000 BTU25 RLA164 LRA |
Blower Motor @ 208/230-3-60 |
N/A 2 hp6.0 Unit FLA |
Unit FLA @ 208/230-3-60 |
N/A 32.5 |
Maximum Fuse Size @ 208/230-3-60 |
N/A 60 |
Minimum Circuit Ampacity @ 208/230-3-60 |
N/A 38.8 |
Operating Power @ 208/230-3-60 |
N/A 8.18 kW |
Compressor @ 460-3-60 |
N/A 83000 BTU12.2 RLA100 LRA |
Blower Motor @ 460-3-60 |
N/A 2 hp2.9 Unit FLA |
Unit FLA @ 460-3-60 |
N/A 15.9 |
Maximum Fuse Size @ 460-3-60 |
N/A 25 |
Minimum Circuit Ampacity @ 460-3-60 |
N/A 19.0 |
Operating Power @ 460-3-60 |
N/A 8.12 kW |
Available Models |
N/A   |
Compressor @ 575-3-60 |
N/A 83000 BTU9 RLA78 LRA |
Blower Motor @ 575-3-60 |
N/A 2 hp2.3 Unit FLA |
Unit FLA @ 575-3-60 |
N/A 12.0 |
Maximum Fuse Size @ 575-3-60 |
N/A 20 |
Minimum Circuit Ampacity @ 575-3-60 |
N/A 14.3 |
Operating Power @ 575-3-60 |
N/A 8.1 kW |
CFM |
N/A 3300 |
Nominal Tonnage |
N/A 6.9 |
Moisture Removal @ 82°DB / 50% R.H.2 | N/A 31.3 LB/HR |
Moisture Removal @ 82°DB / 60% R.H.1 |
N/A 39.8 LB/HR |
Sensible Cooling @ 82°DB / 50% R.H.3 | N/A 45.7 MBH |
Sensible Cooling @ 82°DB / 60% R.H.2 |
N/A 40.6 MBH |
Water Flow4 | N/A 15.0 GPM |
Pressure Drop3 |
N/A 8.2 |
Weight |
N/A 1100 LB |
Refrigerant |
N/A R-410A (Factory Charged 40 lbs.) |
External Static Pressure |
N/A 0.50 " H2O |
Compressor Type |
N/A Scroll |
Filter (Quantity: 4) |
N/A 20" x 25" x 1" Fiberglass |
Drain Connection |
N/A 1" Bar Drain |
Liquid Inlet [O.D.] (up to 50')5 | N/A 0.625 in |
Hot Gas Outlet [O.D.] (up to 50')4 |
N/A 0.875 in |
Water Inlet [O.D.] |
N/A 1.375 in |
Water Outlet [O.D.] |
N/A 1.375 in |
Note |
N/A Ratings are subject to change without notice |
Water Heating Capacity @ 82°DB / 50% R.H. (MBH)6 | N/A 99.1 |
Water Heating Capacity @ 82°DB / 60% R.H. (MBH)1 |
N/A 103.3 |
Water Flow (G.P.M.)7 | N/A 15.0 |
Pressure Drop2 |
N/A 8.2 |
Water Heating Capacity @ 82°DB / 50% R.H. (MBH)8 | N/A 99.1 |
Water Heating Capacity @ 82°DB / 60% R.H. (MBH)1 |
N/A 103.3 |
Water Flow (G.P.M.)9 | N/A 15.0 |
Pressure Drop2 |
N/A 8.2 |
Water Temperature Range10 | N/A 35°F to 85°F |
Available Water Sources |
N/A City Water Geothermal Loop Processed Water Water Tower |
Optional Fresh Air and Discharge Openings |
N/A
DCA3300AWH with Optional Opening, Water Heating Assist Dehumidifier (QUOTE) |
with Indoor Hood (Indoor installation) |
N/A
DCA3300AWH with Indoor Hood, Water Heating Assist Dehumidifier (QUOTE) |
with Outdoor Hood (Outdoor installation) |
N/A
DCA3300AWH with Outdoor Hood, Water Heating Assist Dehumidifier (QUOTE) |