Application
Featuring two modulating analog outputs and two individually programmed relay outputs this system is standard for most DCA dehumidifiers requiring modulating control of auxiliary and on-off control of cooling. A remote temperature sensor is required.
Features
Featuring two modulating analog outputs and two individually programmed relay outputs this system is standard for most DCA dehumidifiers requiring modulating control of auxiliary and on-off control of cooling. A remote temperature sensor is required.
Features
- Based on the Honeywell T775U2006 Universal Electronic Controller
- Easy to use graphical interface
- Individually adjustable set points, differentials and throttling ranges.
- Two analog outputs with selectable 0-10VDC, 2-10VDC and 4-20mA signals
- Two SPDT relay outputs
- Configurable minimum on and off times
- Sensor calibration
- Configurable integral and derivative times
- MPCT-3301: 0 to 10 Vdc heat signal
- MPCT-3302: 2 to 10 Vdc heat signal
- MPCT-3303: 4 to 20 ma heat signal
- TS-W-1097 Wall mounted temperature sensor, 1097 ohm
- TS-D-1097 Duct mounted temperature sensor, 1097 ohm
Unit of Measure
Power Requirements |
N/A
24, 120, or 240 VAC, 50/60 Hz A Separate Earth Ground is Required for Any Power Source |
Power Consumption |
N/A 8 VA Maximum at 60 Hz 10 VA Maximum at 50 Hz |
Operating & Storage Temperature Ambient Rating |
N/A -40ºF to 125ºF (-40ºC to 52ºC) @ 50 Hz -40ºF to 140ºF (-40ºC to 60ºC) @ 60 Hz |
Relative Humidity (Non-Condensing) |
N/A 5 to 95 % |
Relay Contact Output Ratings (N.O. and N.C.) |
N/A 1/2 HP; 4.9 AFL, 29.4 ALR @ 240 VAC 1/2 HP; 9.8 AFL, 58.8 ALR @ 120 VAC 10A @ 24 VAC (Resistive) 125 VA Pilot Duty @ 120/240 VAC |
Modulating Outputs |
N/A 0-10 VDC; Drive A Minimum of 2000 Ohms 2-20 VDC; Drive A Minimum of 2000 Ohms 4-20 mA; Drive A Maximum of 600 Ohms |
Minimum Sensed Temperature Limits |
N/A -60 ºF-51 ºC |
Maximum Sensed Temperature Limits |
N/A 270 ºF132 ºC |
Sensed Temperature Accuracy |
N/A 1ºF/C @ Ambient Room Temperature of 77ºF (25ºC) |
Temperature Setpoint Range |
N/A -40 to 248 ºF-40 to 120 ºC |
Approvals |
N/A UL 60730-1 For US and Canada, CUL, CE, C-TICK |
Time Clock |
N/A Two settable time periods per day are standard on all models |
Volatile Memory |
N/A The date and time settings are retained for 24 hours after the power outage. After a power loss of more than 24 hours, the date and time settings may need to be reentered. All other settings are stored permanently. |
Note |
N/A Ratings are subject to change without notice |