Terms
Application

Featuring two modulating analog outputs and two individually programmed relay outputs, this is a very versatile system for special applications. Remote humidity and/or temperature sensors are required.

Features
  • Based on the Honeywell T775U2016 Universal Electronic Controller
  • Easy to use graphical interface
  • Two inputs: A = Universal, B = Temperature
  • Two analog outputs with selectable 0-10VDC, 2-10 VDC and 4-20mA signals
  • Up to two independent SPDT relay outputs
  • Configurable minimum on and off times
  • Sensor calibration
  • Configurable integral and derivative times
  • Individually adjustable set points, differentials and throttling ranges
Selection
  • MPCTH-3501 Dehumidification, Cooling, Modulating Heat
Accessories
  • HT-W-5 Wall mounted humidity transmitter, 5% RH accuracy
  • HT-D-5 Duct mounted humidity transmitter, 5% RH accuracy
  • TS-W-1097 Wall mounted temperature sensor, 1097 ohm
  • TS-D-1097 Duct mounted temperature sensor, 1097 ohm
Unit of Measure

Type

N/A Dehumidification, Cooling, Modulating Heat

Power Requirements

N/A 24, 120, or 240 VAC, 50/60 Hz
A Separate Earth Ground is Required for Any Power Source

Power Consumption

N/A 8 VA Maximum at 60 Hz 10 VA Maximum at 50 Hz

Operating & Storage Temperature Ambient Rating

N/A -40ºF to 125ºF (-40ºC to 52ºC) @ 50 Hz -40ºF to 140ºF (-40ºC to 60ºC) @ 60 Hz

Relative Humidity (Non-Condensing)

N/A 5 to 95 %

Relay Contact Output Ratings (N.O. and N.C.)

N/A 1/2 HP; 4.9 AFL, 29.4 ALR @ 240 VAC 1/2 HP; 9.8 AFL, 58.8 ALR @ 120 VAC 10A @ 24 VAC (Resistive) 125 VA Pilot Duty @ 120/240 VAC

Minimum Sensed Temperature Limits

N/A -60 ºF-51 ºC

Maximum Sensed Temperature Limits

N/A 270 ºF132 ºC

Sensed Temperature Accuracy

N/A 1ºF/C @ Ambient Room Temperature of 77ºF (25ºC)

Temperature Setpoint Range

N/A -40 to 248 ºF-40 to 120 ºC

Approvals

N/A UL 60730-1 For US and Canada, CUL, CE, C-TICK

Time Clock

N/A Two settable time periods per day are standard on all models

Volatile Memory

N/A The date and time settings are retained for 24 hours after the power outage. After a power loss of more than 24 hours, the date and time settings may need to be reentered. All other settings are stored permanently.

Note

N/A Ratings are subject to change without notice
Site created by Thomas Web Solutions and Powered by Navigator Platform© 2017 Dehumidifier Corporation of America, All Rights Reserved.